12
water to give 50 gpm, but at a reduced temperature. What is
the temperature downstream of point D?
Set 50 gpm in the small window of scale #1. Directly opposite
50 MBH read the temperature difference: 2º. Therefore, the
temperature beyond point D is 200º minus 2º = 198º.
Scale #2 – Flow-Pressure Drop Relationships and
Pipe Sizing
Scale #2 relates gpm ow rate to friction loss rate for both type
“L” copper tubing and for Schedule 40 steel pipe. Friction loss
is stated in terms of milinches per foot and in feet per 100
feet of pipe. Either milinches per foot or feet per 100 feet are
valid expressions of pipe friction loss. Defining these terms:
A. Milinch means 1/1000 of an inch or 1/12,000 of a foot of
pressure energy head.
B. Feet per 100 feet expresses the rate of pipe friction loss as
foot head of energy loss per I 00 feet of pipe.
The pipe friction loss data used as a basis for construction
of scale #2 are The Hydraulic Institute Values, The ASHRAE-
Giesecke Chart Values and The ASHRAE Unified Pressure
Drop Chart data. Both the Hydraulic Institute values and
The ASHRAE Unified Pipe Pressure Drop data are based on
Moody’s pipe pressure drop correlation. Though established
by an entirely different experimental approach, the Giesecke
Chart values closely approximate Moody’s correlation-
generally accepted as most valid. Friction loss indicated for
type “L” copper tubing has been derived from the ASHRAE
Handbook.
Scale #2 is based on a water temperature of 60º. When used
for hot water design with temperatures in the area of 200º
piping pressure drop is over-stated on the order of 10% since
pressure drop decreases slightly as water temperature is
increased. However, the difference is not sufficient to warrant
correction.
The normally used range of pipe friction loss rates is indicated
by a white wedge shape band on scale #2. Experience
indicates that the optimum friction loss range is from 100 to
500 milinches per foot or from approximately 0.85 foot to 4
.5 feet per 100 feet of piping.
Example #1: Determine pipe size for 70 gpm ow rate. Set
the rule so that 70 gpm appears in the “white” or optimum
design range on the rule. It is apparent that either 2½" or 3”
pipe can be used. Setting the arrow to 2½" pipe size in the
iron pipe window, a pipe friction loss rate of 3.6' per 100'
appears opposite 70 gpm. A simultaneous reading on scale
#3 establishes that at 70 gpm a water velocity will be 4.5' per
second.
rate a pipe friction loss rate of 1.2' per 100' will occur. A
simultaneous reading on scale #3 indicates a water velocity of
3.0' per second.
flow-pressure drop-velocity relationship for that particular
pipe size. In the example, either 2½" or 3" piping, could be
used for the
flow rate of 70 gpm, depending on circuit needs,
available pumping head, etc. In many cases, the hydronic
system designer may also wish to evaluate water velocity as
this affects pipe sizing.
Scale #3 – Water Velocity
Scale #3 establishes water velocity in feet per second for
any given flow rate through the particular pipe size. Water
velocity in the hydronic system should be high enough to
carry entrained air in the water stream-yet not high enough to
cause noise. Water velocity should be above 1½ to 2 feet per
second in order to carry entrained air along with the flowing
water to the point of air separation (Rolairtrol, EAS, etc.) where
the air can then be separated from the water and directed to
the compression tank or vented from the system. See other
Bell & Gossett publications for details about air management
in hydronic systems.
Piping noise considerations establish the upper velocity
limitations. For piping 2" and under a maximum velocity of
4 feet per second is recommended. Note that in smaller pipe
sizes, this velocity limitation permits the use of friction loss
rates higher than 4 feet per hundred foot.
Velocities in excess of 4 feet per second are often used on
piping larger than 2 inch. It seems apparent that water
velocity noise is caused by entrained system air, sharp
pressure drops, turbulence, or a combination of these which
in turn cause flow separation, cavitation and consequent
noise in the piping system.
It is generally accepted that if proper air management is
provided to eliminate air and reduce turbulence in the
system, the maximum flow rate can be established by the
piping friction loss rate; at 4 feet per 100 foot. This permits
the use of velocities higher than 4 feet per second in pipe
sizes 2" and larger.
Example #1: A supply main in an apartment building has a
design
flow rate of 1600 gpm. Select the proper pipe size.
Setting Scale #2 at 8" pipe shows that at 1600 gpm, the pipe
friction loss is 3.8 feet per hundred feet. Scale #3 shows that a
water velocity in excess of 10 feet per second will result.
1.2 feet per 100 foot and a water velocity of 6.5 feet per
second, less likely to cause noise. Because the main must
run adjacent to living quarters, a critical location concerning
possible noise generation, the 10" pipe would be preferred.
Scale #4 – Circuit Piping Pressure Drop
Scale #4 provides a simple method of determining required
pump head from the equivalent circuit piping length and the
resistance per unit length. To use Scale #4, it is rst necessary
to establish the total equivalent length (TEL) of the piping
circuit. As all fittings have a greater resistance to flow than
a straight length of pipe, this must be taken into account.
TEL is a summation of the straight lengths of pipe plus the
equivalent length of valves fittings, etc.
In preliminary pipe and pump sizing, it is common practice
to consider the resistance of fittings in a circuit to be a
percentage of the straight length of pipe (usually 50%). In
making a more accurate pressure drop calculation, the actual
resistance of each fitting should be considered. The table on
the back of the System Syzer Calculator envelope indicates
the equivalent length of most commonly used fittings. Recent