120 Braley Rd. P.O. Box 429 East Freetown, MA 02717-0429 www.htproducts.com
LP-200 REV. 1.6.15
SuperStor Contender
Solar Supplement
INSTALLATION
OPERATION
MAINTENANCE
TROUBLESHOOTING
SB Series* Models SE Series** Models
SSC-50SB / SSC-80SB SSC-50SE / SSC-80SE
SSC-119SB SSC-119SE
*With back-up heat exchanger **With back-up electric element
*NOTE: SB Series Model Shown in Drawing
The solar energy system described in this manual, when properly installed and maintained, meets the minimum standards
established by the SRCC. This certification does not imply endorsement or warranty of this product by the SRCC.
NOTICE: HTP reserves the right to make product changes or updates without notice and will not be held liable for typographical errors
in literature.
The surfaces of these products contacted by consumable water contain less than 0.25% lead by weight, as required by the Safe
Drinking Water Act, Section 1417.
NOTE TO CONSUMER: PLEASE KEEP ALL INSTRUCTIONS FOR FUTURE REFERENCE.
2
LP-200 REV. 1.6.15
The following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk
levels, or to important product information.
DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury.
CAUTION used without the safety alert symbol indicates a potentially hazardous situation which, if not avoided, may result in property
damage.
FOREWORD
This manual is intended to be used in conjunction with other literature provided with this Solar Water Heater. This includes all related
control information. It is important that this manual, all other documents included with this system, and additional publications including
Solar Water Heating System Design and Installation Guidelines, SRCC OG-300, be reviewed in their entirety before beginning any
work.
The solar energy system described in this manual, when properly installed and maintained, meets the minimum standards established
by the SRCC. This certification does not imply endorsement or warranty of this product by the SRCC.”
The design of the SuperStor Contender solar system is approved by the Solar Rating and Certification Corporation (SRCC). Any
deviation from the approved specified SRCC components may affect your ability to certify this system.
Installation should be made in accordance with the regulations of the Authority Having Jurisdiction, local code authorities, and utility
companies which pertain to this type of water heating equipment.
Authority Having Jurisdiction (AHJ) The Authority Having Jurisdiction may be a federal, state, local government, or individual such
as a fire chief, fire marshal, chief of a fire prevention bureau, labor department or health department, building official or electrical
inspector, or others having statutory authority. In some circumstances, the property owner of his/her agent assumes the role, and at
government installations, the commanding officer or departmental official may be the AHJ.
NOTE: HTP, Inc. reserves the right to modify product technical specifications and components without prior notice.
FOR THE INSTALLER
INSTALLATION OR SERVICE OF THIS SOLAR WATER TANK IS REQUIRED TO BE PERFORMED BY LICENSED
PROFESSIONALS WHERE SOLAR, PLUMBING AND ELECTRICAL WORK IS REQUIRED.
The installer should be guided by the instructions furnished with the tank, local codes and utility company requirements. Preference
should be given to codes and requirements where they differ from the furnished instructions. Always use the latest edition of codes.
INSTALLATIONS MUST COMPLY WITH:
Local, state, provincial, and national codes, laws, regulations and ordinances.
This manual must only be used by a qualified heating installer/service technician. Read and understand all instructions and safety
messages in this manual before installing, operating, or servicing this water heater. Perform steps in the order given. Failure to comply
could result in substantial property damage, severe personal injury, or death.
3
LP-200 REV. 1.6.15
Solar Water Heating System Design and Installation Guidelines, SRCC OG-300, available from Solar Rating & Certification
Corporation, 400 High Point Drive, Suite 400, Cocoa, FL 32926-6630, www.solar-rating.org.
Code for the Installation of Heat Producing Appliances (latest version), from American Insurance Association, 85 John Street, New
York, NY 11038.
The latest version of the National Electrical Code, NFPA No. 70.
In Canada, refer to Canadian Electrical Code C 22.1, from Canadian Standards Association, 5060 Spectrum Way, Suite 100,
Mississauga, Ontario, Canada L4W 5N6.
TABLE OF CONTENTS
INTRODUCTION .......................................................................................................................................................................... 5
PART 1 - GENERAL SAFETY INFORMATION ........................................................................................................................... 5
A. PRECAUTIONS .......................................................................................................................................................................... 5
B. LOCAL INSTALLATION REGULATION ...................................................................................................................................... 6
C. CHEMICAL VAPOR CORROSION ............................................................................................................................................. 6
D. INSULATION BLANKETS ........................................................................................................................................................... 7
E. DOMESTIC HOT WATER TEMPERATURE ADJUSTMENT ...................................................................................................... 7
F. FREEZE PROTECTION .............................................................................................................................................................. 7
PART 2 IMPORTANT INSTALLATION INFORMATION .......................................................................................................... 7
A. SCOPE OF MANUAL .................................................................................................................................................................. 7
B. LOCAL STANDARDS AND AUTHORIZED PERSONS .............................................................................................................. 7
C. TERMINOLOGY ......................................................................................................................................................................... 7
D. SYSTEM DESIGN ...................................................................................................................................................................... 8
E. FLUID QUALITY ......................................................................................................................................................................... 8
F. CORROSION .............................................................................................................................................................................. 8
G. FREEZE PROTECTION ............................................................................................................................................................. 8
PART 3 - GENERAL SOLAR INFORMATION ............................................................................................................................ 8
A. SYSTEM DESCRIPTION ............................................................................................................................................................ 8
B. SOLAR SYSTEM DESIGN ......................................................................................................................................................... 9
C. SOLAR COLLECTOR INSTALLATION ...................................................................................................................................... 9
D. COLLECTOR ANGLE, PLANE, AND DIRECTION ................................................................................................................... 10
1. COLLECTOR DIRECTION ........................................................................................................................................................... 10
2. COLLECTOR ANGLE (TILT) ........................................................................................................................................................ 10
3. COLLECTOR PLANE (HORIZONTAL OR VERTICAL) ................................................................................................................ 10
E. COLLECTOR PIPING ............................................................................................................................................................... 10
F. COLLECTOR LOOP PIPE INSULATION .................................................................................................................................. 11
G. COLLECTOR SENSOR PLACEMENT ..................................................................................................................................... 11
H. AVOID SHADE ......................................................................................................................................................................... 11
I. LOCATION ................................................................................................................................................................................. 11
J. LIGHTNING PROTECTION ....................................................................................................................................................... 11
K. GALVANIC REACTION ............................................................................................................................................................ 11
4
LP-200 REV. 1.6.15
L. WIND STRESS.......................................................................................................................................................................... 11
M. SNOW LOAD ........................................................................................................................................................................... 12
N. HAIL RESISTANCE .................................................................................................................................................................. 12
O. STORAGE TANKS ................................................................................................................................................................... 12
P. THERMAL EXPANSION (CLOSED LOOP SYSTEMS) ............................................................................................................ 12
PART 4 SPECIFICATIONS ..................................................................................................................................................... 13
PART 5 - INSTALLATION ......................................................................................................................................................... 15
A. INSTALLATION CHECKLIST ................................................................................................................................................... 15
B. SOLAR WATER HEATER LOCATION ..................................................................................................................................... 16
PART 6 PIPING ...................................................................................................................................................................... 16
A. POTABLE WATER PIPING ...................................................................................................................................................... 16
B. WATER CHEMISTRY REQUIREMENTS ................................................................................................................................. 17
C. POTABLE WATER PIPING DETAIL ......................................................................................................................................... 18
D. SOLAR HEAT EXCHANGER PIPING ...................................................................................................................................... 18
E. TANK SENSOR PLACEMENT ................................................................................................................................................. 19
F. NECESSARY COMPONENTS FOR SOLAR WATER HEATER INSTALLATION .................................................................... 19
G. SOLAR WATER HEATER WITH BOILER BACK-UP ............................................................................................................... 21
H. SOLAR WATER HEATER WITH ELECTRIC BACK-UP ........................................................................................................... 22
I. BOILER BACK-UP HEAT EXCHANGER CONNECTION (SB MODELS ONLY) ....................................................................... 23
J. BOILER TANK CONTROL ........................................................................................................................................................ 23
K. CIRCULATOR SIZING .............................................................................................................................................................. 23
L. BOILER BACK-UP HEAT EXCHANGER (SB MODELS ONLY) ............................................................................................... 23
M. ELECTRICAL CONNECTION (SE MODELS ONLY) ............................................................................................................... 24
N. THERMOSTAT ADJUSTMENT ................................................................................................................................................ 25
O. COMBINATION “THERMOSTAT AND HIGH LIMIT CONTROL (ECO)” .................................................................................. 25
PART 7 - FLUID QUALITY ........................................................................................................................................................ 25
A. SOLAR LOOP FLUID QUALITY ............................................................................................................................................... 25
B. FLUID SAFETY LABELING ...................................................................................................................................................... 25
C. FREEZE PROTECTION ........................................................................................................................................................... 25
PART 8 START-UP PREPARATION...................................................................................................................................... 26
A. CHARGING THE SYSTEM ....................................................................................................................................................... 26
B. COMMISSIONING THE SYSTEM ............................................................................................................................................ 26
PART 9 SERVICE/MAINTENANCE PROCEDURES ............................................................................................................. 27
A. SHUTDOWN PROCEDURES ................................................................................................................................................... 27
B. VACATION SHUTDOWN .......................................................................................................................................................... 27
C. ESTIMATED LIFE OF COMPONENTS .................................................................................................................................... 27
D. TEMPERATURE AND PRESSURE RELIEF VALVE................................................................................................................ 27
PART 10 - TROUBLESHOOTING ............................................................................................................................................. 28
A. LEAKS ...................................................................................................................................................................................... 28
B. OTHER PROBLEMS ................................................................................................................................................................. 28
C. OPERATING SUGGESTIONS FOR THE USER ...................................................................................................................... 28
5
LP-200 REV. 1.6.15
PART 11 - SYSTEM PARTS LISTING....................................................................................................................................... 29
A. ESTIMATED COMPONENT LIFE ............................................................................................................................................. 29
B. WARRANTIES AND DISCLAIMERS ........................................................................................................................................ 29
MAINTENANCE NOTES .................................................................................................................................................................. 37
HTP CUSTOMER INSTALLATION RECORD FORM ...................................................................................................................... 38
INTRODUCTION
Your solar water heater has an internal solar heat exchanger for use with solar collectors. When there is not sufficient solar energy, the
water heater utilizes a backup system to provide hot water. In SB Series water heater models, the tank has an extra heat exchanger
that connects to a boiler. In SE Series models, the water heater has an electric heating element. (Refer to solar piping details in this
manual for suggested piping applications of both models.)
Your solar system uses a circulation pump to circulate a propylene glycol/water heat transfer fluid solution (HTF) throughout a closed
loop system. Closed loop propylene glycol systems provide freeze protection for the solar components.
This manual intends to familiarize you with the proper installation and maintenance of your solar water heating system. This system
must be installed by a licensed solar or plumbing contractor in accordance with SRCC Standard OG-300 and all applicable national,
state, and local codes.
Job site conditions will require your installation contractor to supply some or all of the following:
Plumbing Connections
Piping and Insulation
Valves Between the Existing Domestic Water System and the Solar System
NOTE: Solar system performance and efficiency varies with factors such as: household hot water load, ambient air temperature,
collector/roof pitch, collector orientation, and seasonal intensity.
NOTE: Failure to follow the procedures described in this manual WILL VOID the warranty.
PART 1 - GENERAL SAFETY INFORMATION
INSTALLER Read all instructions in this manual before installing. Perform steps in the order given.
USER This manual is for use only by a qualified heating installer/service technician. Have this solar water heating system
serviced/inspected by a qualified service technician annually.
FAILURE TO ADHERE TO THE GUIDELINES ON THIS PAGE AND HAVE THIS SOLAR WATER HEATING SYSTEM
SERVICED/INSPECTED ANNUALLY CAN RESULT IN SUBSTANTIAL PROPERTY DAMAGE, SEVERE PERSONAL INJURY, OR
DEATH.
A. PRECAUTIONS
NOTE: When inquiring about service or troubleshooting, reference the model and serial numbers from the solar water heater rating
label.
NOTE: OBTAIN ALL APPLICABLE PERMITS AND OBEY ALL LOCAL CODES.
NOTE: If any component of the solar water heating system is exposed to the following, do not operate until all corrective steps have
been made by a qualified serviceman:
1. FIRE
2. DAMAGE
3. WATER
Any claims for damage or shortage in shipment must be filed immediately against the transportation company by the consignee.
Be sure to disconnect electrical power from the solar water heating system before performing service. Failure to do so could result in an
electrical shock, property damage, serious personal injury, or death.
6
LP-200 REV. 1.6.15
DO NOT USE THIS SOLAR WATER HEATING SYSTEM IF ANY PART HAS BEEN SUBMERGED IN WATER. Immediately call a
qualified service technician. Components MUST BE replaced if submerged. Attempting to operate a solar water heating system that
has been even partially submerged could create numerous harmful conditions, such as a potential gas leakage causing a fire and/or
explosion, or the release of mold, bacteria, or other harmful particulates into the air. Operating a previously submerged solar water
heating system could result in property damage, severe personal injury, or death.
NOTE: Damage due to flood or submersion is considered an Act of God, and IS NOT covered under product warranty.
NOTE: Install all system components and piping in such a manner that does not reduce the performance of any fire rated assembly.
Improper installation or use may result in property damage. Such damage IS NOT covered by warranty.
NOTE: HTP DOES NOT WARRANT THIS WATER HEATER AGAINST FREEZE RELATED DAMAGE.
ALL PIPING AND PLUMBING CONNECTIONS IN CLOSED LOOP SYSTEMS SHOULD BE MADE WITH COPPER PIPE ONLY. No
less than ¾” I.D. copper tube of the type meeting local codes must be used for piping. Pipe runs must be solidly attached with proper
clamping methods. Soldered connections should be secured with 95/5 lead-free solder. Use only pipe rated for 250
o
F minimum on both
the collector return and supply piping.
Only use this solar hot water system as intended and described in this installation manual. Any use other than described will void
warranty and may lead to fire, property damage, personal injury, or death.
High heat sources (sources generating heat 100
o
F / 37
o
C or greater, such as stove pipes, space heaters, etc.) may damage plastic
components of the water heater as well as plastic vent pipe materials. Such damages ARE NOT covered by warranty. It is
recommended to keep a minimum clearance of 8” from high heat sources. Observe heat source manufacturer instructions, as well as
local, state, provincial, and national codes, laws, regulations and ordinances when installing this water heater and related components
near high heat sources.
B. LOCAL INSTALLATION REGULATION
Installation of this solar water heater may be governed by individual local rules and regulations for this type of product, which must be
observed. Always use the latest edition of codes. The installation, adjustment, service, and maintenance of the solar water heater must
be done by a licensed professional who is qualified and experienced in the installation, service, and maintenance of solar hot water
systems.
C. CHEMICAL VAPOR CORROSION
NOTE: DAMAGE TO THE SOLAR WATER TANK, COLLECTOR, OR RELATED COMPONENTS CAUSED BY EXPOSURE TO
CORROSIVE VAPORS IS NOT COVERED BY WARRANTY. The limited warranty is voided when failure of water tank is due to a
corrosive atmosphere. (Refer to the limited warranty for complete terms and conditions).
PRODUCTS TO AVOID
AREAS LIKELY TO HAVE CONTAMINANTS
Spray cans containing fluorocarbons
Dry cleaning/laundry areas and establishments
Permanent wave solutions
Swimming pools
Chlorinated waxes/cleaners
Metal fabrication plants
Chlorine-based swimming pool chemicals
Beauty shops
Calcium chloride used for thawing
Refrigeration repair shops
Sodium chloride used for water softening
Photo processing plants
Refrigerant leaks
Auto body shops
Paint or varnish removers
Plastic manufacturing plants
Hydrochloric or Muriatic acid
Furniture refinishing areas and establishments
Cements and glues
New building construction
Antistatic fabric softeners used in clothes dryers
Remodeling areas
Chlorine-type bleaches, laundry detergents, and cleaning solvents
Garages and workshops
Adhesives used to fasten building products
Table 1 Chemical Contaminants
7
LP-200 REV. 1.6.15
D. INSULATION BLANKETS
For installation of insulation blankets, refer to Solar Water Heating System Design
and Installation Guidelines, SRCC OG-300.
E. DOMESTIC HOT WATER TEMPERATURE ADJUSTMENT
An ASSE 1017 rated mixing valve to avoid severe burns or death from scalding
temperature IS REQUIRED PER SRCC OG-300.
Households with small children, disabled, or elderly persons may require a
120
o
F or lower temperature setting to prevent severe personal injury or death
due to scalding.
F. FREEZE PROTECTION
NOTE: Consider piping and installation when determining heater location. Place
heater in location not prone to freezing.
Failure of the solar system due to freeze related damage IS NOT covered by warranty.
In order to meet health and safety regulations, solar system antifreeze fluid should be food grade polypropylene glycol, FDA rated as
“generally recognized as safe” (GRAS). The recommended glycol is DOWFROST or equivalent. Using proper concentrations of glycol,
solar systems can be operated at ambient temperatures as low as -60
o
F. Freeze tolerance limits are based upon an assumed set of
environmental conditions. Refer to the specification sheet included with the glycol for recommended concentrations. A glycol/water mix
must not exceed 50%, unless the manufacture specifies that a different ratio is recommended for use with solar water heaters. Glycol
may need to be changed periodically (every 3-5 years) to prevent it from becoming acidic; please refer to the guidelines provided by the
glycol manufacturer regarding replacement.
PART 2 IMPORTANT INSTALLATION INFORMATION
A. SCOPE OF MANUAL
This manual pertains only to the installation and operation of the HTP SuperStor Ultra solar water heater. Details for the installation,
operation, and maintenance of the complete solar water heating system, including, but not limited to: the solar collector(s), boiler, pump,
system controller, valves, and other plumbing components, should be provided separately by their respective manufacturers.
NOTE: This manual is primarily a reference document for authorized persons, as the solar water heater is not permitted to be installed
by non-authorized persons.
B. LOCAL STANDARDS AND AUTHORIZED PERSONS
Installation must be completed in accordance with local standards and regulations.
Installation must also be completed by a qualified tradesperson who holds relevant industry licenses or certificates. The term
“authorized person(s)” refers to a suitably qualified professional. Unless otherwise specified, no part of the HTP solar water heater may
be inspected, repaired, or maintained by anybody other than an authorized person.
C. TERMINOLOGY
Solar terminology differs from region to region. To avoid confusion, please note the following:
Supply The plumbing line running from the outlet of the collector to the tank (or heat exchanger).
APPROXIMATE TIME / TEMPERATURE RELATIONSHIPS IN SCALDS
More than 5 minutes
1 ½ to 2 minutes
About 30 seconds
About 10 seconds
Less than 5 seconds
Less than 3 seconds
About 1 ½ seconds
About 1 second
Table 2
8
LP-200 REV. 1.6.15
Return The plumbing line running from the tank (or heat exchanger) to the inlet of the collector. This line incorporates the circulation
pump.
D. SYSTEM DESIGN
PRESSURIZED CLOSED LOOP SYSTEMS
A closed loop system uses non-potable HTF and must be pressurized to less than 72.5 psi. Closed loop systems require an expansion
tank to accommodate HTF expansion. The system should be designed to minimize stagnation after the tank temperature has been met;
extensive stagnation may increase pH levels and glycol deterioration.
The expansion tank and plumbing must be properly sized so that the safety pressure relief valve will not activate except in the event of
component failure or extreme conditions. The pressure release must be set at no more than 90 psi. (There may be exceptions in
engineered designs for tall buildings.)
E. FLUID QUALITY
Water quality is very important. Water in direct flow through the solar collectors must first meet potable water requirements; any fluid
circulated through the collectors should be non-corrosive to copper. In addition, water quality must meet the following requirements.
Hardness: Less than 7 grains
Chloride levels: Less than 100 ppm
pH levels: 6-8
TDS: Less than 2000 ppm
Sodium: Less than 20 mGL
In order to meet health and safety regulations, glycol used should be food grade propylene glycol, FDA rated as “generally recognized
as safe” (GRAS). If using a glycol/water mix, distilled water is preferred. If distilled water is unavailable, the water must meet the above
requirements. The glycol content of the liquid must not exceed 50%, unless the manufacturer specifies that a different ratio is
recommended for use with solar water heaters. Glycol should be checked periodically to prevent it from becoming acidic. Please refer
to guidelines provided by the glycol manufacturer regarding glycol maintenance.
F. CORROSION
Both copper and stainless steel are susceptible to corrosion when, amongst other factors, high concentrations of chlorine are present.
NOTE: Leakage of the solar water heater due to corrosion caused by improper water quality IS NOT covered by product warranty.
G. FREEZE PROTECTION
Freeze protection must be implemented in any regions that may experience freezing conditions at any time throughout the year.
“Freeze tolerance limits are based upon an assumed set of environmental conditions. Extended periods of cold weather, including
ambient air temperatures below the specified limit, may cause freezing in exposed parts of the system. It is the owner’s responsibility to
keep the system’s freeze protection levels maintained in accordance with the supplier’s instructions if the air temperature is expected to
approach the specified freeze tolerance limit.”
Closed loop systems: In areas with temperatures not falling below 23
o
F, a differential solar controller with freeze protection may be
used (e.g. requiring pump to circulate if the manifold temperature approaches freezing). In an open loop system, a freeze valve (which
opens to allow water to dribble out) could also be considered.
Closed loop systems: In areas with temperatures falling below 23
o
F, a propylene glycol/water mix should be used to provide freeze
protection. Please refer to glycol manufacturer’s specifications about the temperature ranges the liquid can withstand. Only food grade
propylene glycol, FDA rated as GRAS, should be used.
NOTE: HTP DOES NOT WARRANT THE SOLAR WATER HEATER AGAINST FREEZE-RELATED DAMAGE.
PART 3 - GENERAL SOLAR INFORMATION
A. SYSTEM DESCRIPTION
By using the sun’s energy to heat water, solar hot water heating systems help reduce the nation’s dependence on polluting fossil fuels.
This reliable, efficient solar water heater meets the certification requirements of SRCC-OG-300.
Basic components of the solar water heating system include: the solar collector(s), a solar water heater, a circulator pump, a differential
solar control, and an expansion tank. The types of solar systems in which the solar water heater can be installed include:
9
LP-200 REV. 1.6.15
Pressurized Closed Loop Systems These systems use a glycol/water mix as HTF, which protects the system from freezing. These
systems operate at high pressures.
In systems using a glycol/water mix, freeze protection fluid must be non-toxic propylene glycol, FDA rated as GRAS. To protect the heat
exchanger and other system components, regular scheduled maintenance must be established to monitor and maintain proper HTF pH
levels.
Do not introduce HTF into any fittings on the heater except those clearly marked for that purpose.
The system components should carry temperature and pressure ratings equivalent to the design of the solar collector. To ensure
system is appropriate for the installation climate, the solar collector ratings should be verified against the collector manufacturer
specifications. Collector and storage tank temperatures can be read from the system controllers. Typical tank operating temperatures
range from 40-80
o
F on the cold supply line to the 175
o
F tank high limit. The collector temperature sensor should be 5-20
o
F higher than
the tank sensor during normal charging operation. During idle period, when there is no sun, the collector sensor will read the ambient
temperature; in full sun, the sensor will read as high as 250
o
F. Temperatures vary depending on installation climate.
Using proper concentrations of glycol, solar systems can be operated at ambient temperatures as low as -60
o
F. Freeze tolerance limits
are based upon an assumed set of environmental conditions. Refer to the manufacturer’s specification sheet for recommended
concentrations.
Depending on the controller model, the differential controller uses 10k ohm thermistors or 1k ohm RTDs to monitor the temperature
difference between the collector and the solar water heater. The controller turns on when the collector is 12-20
o
F above tank
temperature and turns off when the differential drops to 4
o
F.
B. SOLAR SYSTEM DESIGN
System design should be completed prior to installation. Solar collectors need to be installed correctly to ensure high efficiency and,
most importantly, safe and reliable operation. Please seek professional advice for the design and installation of your solar heating
system.
NOTE: Only authorized licensed contractors are permitted to install the solar collector.
C. SOLAR COLLECTOR INSTALLATION
NOTE: The solar collector instructions are general in nature. Reference the solar collector manufacturer’s instructions for more specific
and detailed installation information.
The solar collector installation contractor shall obtain all required permits and approvals when installing the solar system. The
installation shall conform to all federal, state and local regulations governing solar water heating system installations. The contractor
shall adhere to sound building safety and trade practices. Special consideration must be given to building code requirements for the
penetration of structural members and fire rated assemblies.
All persons working on roofs should have completed a fall safety course and must be properly outfitted with appropriate safety
equipment. Failure to follow this information could result in property damage, severe personal injury, or death.
Before installation, the contractor shall inspect the condition of the roof and notify the homeowner of any existing roof damage or
necessary repairs. The most important structural consideration is to securely anchor the solar collector and solar strut mounting
hardware to the structural members of the roof with stainless steel hanger or lag bolts. Consult with the collector manufacturer
installation manual for proper guidelines in your application.
Solar collectors should be covered at all times until installation is complete. Failure to follow this information could result in severe
personal injury or death.
Preserving the integrity of the roof membrane is the most important roofing consideration. Ensure that all roof penetrations required to
plumb and mount the solar collector are properly flashed and sealed in accordance with standard roofing practices. The recommended
elastomer for sealing roof penetrations is Tremco “POLYroof”.
10
LP-200 REV. 1.6.15
D. COLLECTOR ANGLE, PLANE, AND DIRECTION
1. COLLECTOR DIRECTION
The collector should face the equator. In the northern hemisphere, this is due south, and in the southern hemisphere, due north. Facing
the collector in the correct direction and angle is important to ensure
optimal heat output. A deviation of up to 15
o
from due south is
acceptable, and will have minimal effect on heat output.
2. COLLECTOR ANGLE (TILT)
It is common for collectors to be installed at an angle that corresponds
to the installation latitude. While adhering to this guideline, an angle of
latitude +/- 10
o
is acceptable, and will not greatly reduce solar output.
The solar collector should be installed at an angle of between 20 80
o
to ensure optimal operation.
For year-round domestic hot water, the collector should be tilted to an
angle of equal to the latitude of the installation site. Add 15
o
to the
latitude to optimize for winter performance (space heating). Subtract
15
o
from the latitude to optimize for summer performance (pool
heating).
Given the formula above, a solar collector installed at 30
o
N latitude
should face due south at an angle of 45
o
for wintertime advantage, and
15
o
for summertime heating.
Preventing Overheating
To reduce summer heat output, angle the collector for optimal winter
absorption. This is achieved by installing the collector at an angle of around 15
o
above the latitude angle (e.g. 45
o
at 30
o
N latitude). This
angle corresponds closely to the angle of the sun in the sky during the winter months, thus maximizing winter output. Conversely,
during the summer when the sun is high in the sky, the relative collector surface area exposed to sunlight is reduced, cutting overall
heat production considerably (by about 15%). This option is ideal for installations where solar thermal is being used for space heating.
3. COLLECTOR PLANE (HORIZONTAL OR VERTICAL)
The collector could be installed vertically, but may be installed at an angle, such as sideways on a pitched roof. In vertical installations,
collectors may be installed level, or with ¼” pitch towards the return port. See more detail in Part 2, Section D, Number 3.
E. COLLECTOR PIPING
Never use dielectric unions or galvanized steel fittings in the collector loop. Doing so will lead to corrosion, property damage, and
possible early water heater failure. Such damage IS NOT covered by warranty. Use only copper and brass fittings.
Collector piping requires the use of copper and brass fittings in the collector loop. To
avoid leaks and fluid loss, copper and brass ground joint unions should be used to join
the collectors. Use only lead-free solder. Engelhard Silvabrite 100 or equivalent is the
required soldering material. Use of 50/50 lead solder is expressly prohibited. Use of
galvanized steel, CPVC, PVC or any other non-rated plastic pipe is prohibited.
Penetrations through walls or other surfaces shall not allow intrusion by insects and/or
other vermin. Ensure that all structural penetrations are properly sealed with an
elastomer, such as Tremco “POLYroof”.
Piping in new solar installations may have dirt, grease, solder flux, or other impurities
that will affect the quality of HTF over time. Thorough cleaning is required before
charging new solar installations with glycol.
Ensure that there are no dips or low points in solar piping that could trap fluid and possibly rupture in freezing conditions. Copper
plumbers tape or tube strap is the required strapping material. The pipe insulation may not be compressed or crimped by the strapping
material.
The installation of all piping may not reduce the performance or rating of structural members or fire rated assemblies and must adhere
to all applicable local codes and ordinances.
Figure 1 - Suggested placement of solar collectors
Figure 2 Sensor Placement
11
LP-200 REV. 1.6.15
F. COLLECTOR LOOP PIPE INSULATION
The collector loop supply and return lines must be well insulated with high quality, flexible, closed cell insulation to minimize heat loss.
Wall thickness of pipe insulation should not be less than ¾". 1" wall thickness is required in all areas prone to annual hard freeze
conditions. When it comes to pipe insulation the rule is simple: thicker is better. The specified insulation material is HT/Armaflex or
equivalent.
Whenever possible, slide the insulation material over the pipe without cutting or taping. All butt joints must be sealed with contact
adhesive. HT/Armaflex should be sealed with Armaflex HT 625 adhesive. Use of rigid polyethylene pipe insulation is prohibited.
Temperatures generated by your collector in the summer months or under stagnation conditions can melt this type of material.
Any above ground exterior pipe insulation is subject to UV degradation and must be wrapped with PVC pipe wrap or painted with two
coats of high quality water-based acrylic resin coating as supplied by the insulation manufacturer. Foil tape should not be used as it will
fail. The required coating material is Armaflex WB Finish or equivalent. Prior to applying finish, wipe insulation clean with denatured
alcohol. Paint insulation with two coats of finish. Do not tint the finish.
G. COLLECTOR SENSOR PLACEMENT
The collector sensor must be located on the hot water return line as close to the collector as possible. Some collectors have insertion
wells to measure temperatures more accurately at the manifold.
Sensors are typically accurate to +/ 1/2 °F if properly installed and weatherized. To maximize sensor accuracy, attach the flanged
portion of the sensor to the collector header pipe with a stainless steel hose clamp. Wire nuts used to connect the sensor and low
voltage wiring shall be all plastic, sealed with silicone and thoroughly wrapped in electrician's tape.
The low voltage wiring used to connect the sensors to the controller should be a minimum 18 AWG. The wiring should be bare or tinned
copper, two conductor, PVC insulated, with a PVC UV rated gray jacket suitable for exterior use. Use Eastman Wire & Cable no. 5704,
Beldon Wire and Cable no. 8461 or equivalent.
The sensor must be placed on the solar collector return line as close to the collector header as possible. Place the sensor wire over the
rubber pipe insulation, under the insulation tape or PVC pipe wrap. Thoroughly wrap and weatherize the insulation with electrician's
tape or insulation tape as provided by the manufacturer.
H. AVOID SHADE
Collectors should be located so that shading does not occur between 9 AM and 3 PM local time. Partial shading due to small objects
such as antennas and flues is not of great concern.
I. LOCATION
To avoid long pipe runs, the collector should be positioned as close as possible to the storage tank. Storage tank location should
therefore be considered part of the location requirements of the solar collector. The storage tank should be located as close as possible
to the most frequent draw off points in the building.
J. LIGHTNING PROTECTION
To avoid lightning related damage or electrical safety issues, it is advisable to earth/ground the frame and copper circulation loop of the
collector.
K. GALVANIC REACTION
Zinc galvanized components should NOT be installed in direct contact with stainless steel or aluminum, as galvanic reaction between
metals can cause premature oxidation of the zinc coating, as well as the steel and aluminum underneath.
Avoid using galvanized steel bolts. Use stainless steel components instead. If galvanized components ARE used, avoid direct contact
between two metals by using rubber/plastic separators.
If roof surface is galvanized steel, refer to manufacturer’s corrugated roof installation guidelines.
L. WIND STRESS
When installing the solar collector(s), please consider the issue of wind resistance and the resultant stress on attachment points.
Adhere to relevant building codes/regulations regarding installation of such objects.
It is the responsibility of the installation contractor to ensure that the frame mounting is of suitable strength. Where applicable,
inspection by building department officer or equivalent should be completed to ensure the installation is in accordance with relevant
regulations.
12
LP-200 REV. 1.6.15
M. SNOW LOAD
In areas prone to heavy snowfall, the solar collector(s) should ideally be installed at an angle of 50
o
or greater to help promote snow
sliding off the collectors. In addition, it is advisable to raise the lower collector frame off the roof surface 6 8 inches or higher. Doing
this places the collector above moderate snowfall accumulation and allows drifting snow to more easily slide out from under the
collector, which helps ensure that snow does not cover the collector array.
Please refer to local regulations regarding snow loading precautions.
N. HAIL RESISTANCE
Solar collectors are surprisingly strong and able to handle significant impact stresses once installed. Testing and impact stress
modeling proves that when installed at an angle of 40
o
or greater, collectors are able to withstand impact from hail larger than 1” in
diameter. The ability of collectors to withstand hail impact is greatly influenced by the angle of impact, so installing the collectors at low
angles does reduce their impact resistance.
O. STORAGE TANKS
It is recommended that the lever on the pressure and temperature relief valves (PTRV) on main pressure hot water storage tanks be
operated once every 6 months to ensure reliable operation. It is important to raise and lower the lever gently, and be careful as the
water released will be HOT. Failure to operate the PTRV on a regular basis could lead to failure of the component and the possibility of
the storage tank exploding.
It is recommended, and may also be a local regulation, that, in order to expel water safely, the PTRV have a copper pipe connected
and run to an appropriate drainage location. The PTRV and drain outlet pipe must not be sealed or blocked.
NOTE: If the water heater is left in an operating condition and not used for two weeks or more, a quantity of highly flammable hydrogen
may accumulate in the top of the water cylinder.
To dissipate hydrogen safely, it is recommended that a hot water tap be turned on for several minutes at a sink, basin, or bath, but not a
dishwasher, clothes washer, or other electrical or heat producing appliance. During this process, there must be no smoking, open
flame, or electrical appliance operating nearby. Hydrogen discharged through the tap will sound like air escaping. Failure to dissipate
hydrogen properly could result in explosion and fire, serious property damage, severe personal injury, or death.
P. THERMAL EXPANSION (CLOSED LOOP SYSTEMS)
As water is heated, it expands. This is known as thermal expansion. Thermal expansion can cause premature component failure. Such
failures ARE NOT covered under product warranty.
An expansion tank, properly sized for your solar system, should be installed to control thermal expansion. Refer to expansion tank
manufacturer’s specifications for proper sizing guidelines.
13
LP-200 REV. 1.6.15
PART 4 SPECIFICATIONS
Figure 3 SB Series Water Heater Dimensions and Specifications
14
LP-200 REV. 1.6.15
Figure 4 SE Series Water Heater Dimensions and Specifications
15
LP-200 REV. 1.6.15
PART 5 - INSTALLATION
A. INSTALLATION CHECKLIST
Location
Sufficient room to service water heater, piping, and related controls
Provisions made to protect area from water damage
Centrally located to fixtures
Protected from freezing temperatures
Area free of flammable and/or corrosive vapors
Potable Water Supply
All related piping free from leaks
Thermal expansion tank installed
Water heater and fixtures have been properly purged of air
ASSE 1017 rated thermostatic mixing valve IS REQUIRED PER SRCC OG-300
Have water supply tested and ensure it meets the requirements outlined in the Part 2, Section E of this manual
Relief Valve
Temperature and Pressure relief valve properly installed and discharge line runs to open drain
Discharge line not exposed to freezing temperatures
Discharge line constructed of copper
Wiring; SE models
Power supply voltage agrees with the water heater rating plate
Branch circuit wire fusing or circuit breaker properly sized
Electrical connections tight and unit properly grounded
Wiring; SB models
Water heater control is secure and in control well
Boiler backup control is wired to the boiler control or relay center
Solar Heat Exchanger to Solar Panel; SE and SB models
Anti-freeze (if used) is added and rated as non-toxic with copy of MSDS sheet for homeowner
Solar heat exchanger completely purged of air
Expansion tank and temperature and pressure gauge operating properly
Solar control shows circulators operating properly on the solar panels
Boiler Heat Exchanger; SB models only
Boiler heat exchanger completely purged of air
Expansion tank and temperature and pressure gauge operating properly
Boiler control shows circulators operating properly on the solar panels
Anti-Freeze Fluid (if used in system)
Make sure freeze protection fluids are certified non-toxic, FDA rated GRAS
Glycol percentage must be calculated per local area freeze level
Provide glycol MSDS sheet to end user
NOTE: Make sure you have all necessary tools, materials and accessories before beginning work on the solar system.
TOOLS AND MATERIALS
Electric Drill Torch and Striker
Drill Index (w/ ½”, ¾”, 1” and 1 ¼” Wood Bits) Putty Knife
Hack Saw High Temperature Joint Compound
Tubing Cutter Wire Nuts or Connectors
Tin Snips Miscellaneous Copper Pipe & Fittings (3/4”)
16’ Tape Measure 1” x ¾” Copper Sweat Couplings
24” Level 1” Copper Sweat Caps
Flashlight Silicon Caulk and Roof Sealant
Extension Cord Minimum ¾” I.D. Type M Copper Tubing
Slip Joint Pliers Needle Nose Pliers
Pipe Wrenches, 10” and 14” Angle Iron
Open End Wrenches, 9/16 & 7/16 Threaded Rod, Nuts, & Washers
Screw Driver 6” Flat Blade Stainless Screw Clamps
Screw Driver 6” Philips Thermal Adhesive
16
LP-200 REV. 1.6.15
Wire Stripper or Knife Aluminum Flashing Sheet
Wire Cutters Black Latex Outdoor Paint
Adjustable Wrenches 8” & 10” 7/8” x ¾” and 1 1/8” x ¾” pipe insulation
Solder Flux Emory Paper
B. SOLAR WATER HEATER LOCATION
To minimize expense and heat loss, locate the solar water
heater as centrally to the domestic piping system and near the
solar collectors as possible. The water heater must also be
located in an area where it will not be exposed to freezing
temperatures. All piping should be insulated to protect against
freezing and heat loss.
In addition, the solar water heater and all related solar system
components should be installed with plenty of clearance for
inspection and service. If minimum clearances are not met, it
may not be possible to service the solar system without
removing component parts from installation locations.
The solar water heater should also be installed in a place where
T&P discharge or a leak will not result in damage to the
surrounding area. Install a 2” high catch pan with a minimum of
¾” drain line to prevent water damage if leakage should occur
(see Figure 5).
Filled hot water storage tanks are very heavy, and should be
located in areas that can structurally support such weight.
Failure to properly locate water storage tanks could result in
property damage, personal injury, or death.
PART 6 PIPING
The design and installation of the solar water heating system
should be done by qualified individuals. It is important that good
design and installation practice be followed to assure that your
system will operate properly. Failure to follow installation
guidelines for you solar water heater system could cause
component failure and possible safety issues.
A. POTABLE WATER PIPING
It is very important that you do the potable piping before you pipe into your solar system. Failure to do so may damage your water
heater.
Do not introduce HTF into any fittings on the heater except those clearly marked for that purpose.
It is mandatory that all plumbing be done in accordance with local and state codes or warranty will be void. It is also necessary to use
both thread tape and pipe dope on all mechanical connections. The potable water piping is located on the side of your solar water
heater and marked Hot and Cold. It is recommended that unions or flexible copper connectors be used so heater can be easily
serviced. Install a shut-off valve on the cold feed near the solar water heater to isolate the tank for future service.
Provide clear access to the storage tank, pump, expansion tank, mixing valve, time clock and other key components. The components
on the potable side of the system may require future service or maintenance, so it is recommended that the connections be made with
brass unions. You must use copper and brass fittings in plumbing the solar storage tank and expansion tank. The use of galvanized
fittings, nipples, dielectric unions, CPVC, PVC, or other plastic pipe is prohibited.
Hard copper connections to the city cold water supply line and home hot water feed lines are recommended.
Figure 5 Catch Pan Installation and Recommended Service
Clearances
17
LP-200 REV. 1.6.15
The gaskets in standard water heater flex hose connectors can become brittle and compressed over time and begin leaking on the
water heater. If not detected in a timely manner, a drip or leak may cause serious damage to the tank’s electrical components, or, in
extreme cases, cause the tank to leak from the outside in.
B. WATER CHEMISTRY REQUIREMENTS
Chemical imbalance of the water supply may affect efficiency and cause severe damage to the water heater and associated equipment.
HTP recommends having water quality professionally analyzed to determine whether it is necessary to install a water softener. It is
important that the water chemistry on both the domestic hot water and central heating sides are checked before installing the water
heater, as water quality will affect the reliability of the system. Failure of a water heater due to lime scale build-up, low pH, or other
chemical imbalance IS NOT covered by the warranty.
Operating temperatures above 135
o
F will further accelerate the build-up of lime scale and may shorten the service life of the water
heater. Failure of the water heater due to lime scale build-up on the heating surface, low pH, or other chemical imbalance IS NOT
covered by the warranty.
Outlined below are water quality parameters which need to be met in order for the system to operate efficiently for many years.
Water Hardness
Water hardness is mainly due to the presence of calcium and magnesium salts dissolved in water. The concentration of these salts is
expressed in mg/L, ppm, or grains per gallon as a measure of relative water hardness. Grains per gallon is the common reference
measurement used in the U.S. water heater industry. Hardness expressed as mg/L or ppm may be divided by 17.1 to convert to grains
per gallon. Water may be classified as very soft, slightly hard, moderately hard, or hard based on its hardness number. The minerals in
the water precipitate out as the water is heated and cause accelerated lime scale accumulation on a heat transfer surface. This lime
scale build-up may result in premature failure of the water heater. Operating temperatures above 135
o
F will further accelerate the build-
up of lime scale and may shorten the service life of the water heater.
Water that is classified as hard and very hard must be softened to avoid water heater failure.
CLASSIFICATION
MG/L OR PPM
GRAINS/GAL
Soft
0 17.1
0 - 1
Slightly Hard
17.1 60
1 3.5
Moderately Hard
60 120
3.5 7.0
Hard
120 180
7.0 10.5
Very Hard
180 and over
10.5 and over
If the hardness of the water exceeds the maximum level of 7 grains per gallon, water should be softened to a hardness level no lower
than 5 grains per gallon. Water softened as low as 0 to 1 grain per gallon may be under-saturated with respect to calcium carbonate,
resulting in water that is aggressive and corrosive.
pH of Water
pH is a measure of relative acidity, neutrality or alkalinity. Dissolved minerals and gases affect water pH. The pH scale ranges from 0 to
14. Water with a pH of 7 is considered neutral. Water with a pH lower than 7 is considered acidic. Water pH higher than 7 is considered
alkaline. A neutral pH (around 7) is desirable for most potable water applications. Corrosion damage and tank failures resulting
from water pH levels of lower than 6 or higher than 8 ARE NOT covered by the warranty. The ideal pH range for water used in a
water heater is 7.2 to 7.8.
Total Dissolved Solids
Total Dissolved Solids (TDS) is a measurement of all minerals and solids dissolved in a water sample. The concentration of total
dissolved solids is usually expressed in parts per million (ppm).
Water with a high TDS concentration will greatly accelerate lime and scale formation in the hot water system. Most high TDS
concentrations precipitate out of the water when heated. This can generate a scale accumulation that will greatly reduce the service life
of a water heater.
The manufacturer of the water heater has no control over water quality, especially TDS levels in your system. Total dissolved solids in
excess of 2,000 ppm will accelerate lime and scale formation on the element or heat exchanger. Water heater failure due to total
dissolved solids in excess of 2,000 ppm is a non-warrantable condition. Failure of a water heater due to lime scale build up IS NOT
covered by the warranty.
Hardness: 7 grains
Chloride levels: 100 ppm
pH levels: 6-8
18
LP-200 REV. 1.6.15
TDS: 2000 ppm
Sodium: 20 mGL
C. POTABLE WATER PIPING DETAIL
Figure 6 - This drawing is meant to demonstrate potable piping concept only.
D. SOLAR HEAT EXCHANGER PIPING
Set up the primary balance of the system components following the piping detail in Figure 6.
Run ½” type M or larger copper pipes, or flex line sets, to and from the collector following the direction of supports, penetrations, and
other relative items.
Only copper, cast iron, or brass are to be allowed in the collector piping loop due to transient operating temperatures that may reach as
high as 300
o
F. PEX, PVC, CPVC, and other polymers are expressly prohibited in the piping network of closed loop systems.
19
LP-200 REV. 1.6.15
When making a connection to the heat exchanger, use Teflon Tape and joint compound to prevent leaks. The connections to the heat
exchanger are 1” NPT. Do not apply heat directly to the heat exchanger thread connection when sweating fittings.
Line pressure and temperature gauge shall be installed in the collector supply and return lines to allow for a simple diagnostic check of
proper system operation. On a sunny day, the hot water return line should be approximately 5 12
o
F warmer than the water in the
collector supply line. Compare the temperature readings in the two line thermometers. The ¾” cold water supply line to the storage tank
must be insulated with a minimum 7/8” x ½” pipe insulation to a minimum distance of 5’ behind the storage tank, or to the wall if closer
than 5’.
E. TANK SENSOR PLACEMENT
Make sure the sensor is secured on the stud located in the lower section of the water heater. Secure the sensor by packing Armaflex
insulation behind it. This will also help the sensor react to temperature change.
Non-toxic freeze protection fluid must be used to protect the system from freezing. Use a mixture appropriate for your climate. Do not
use a higher glycol to water concentration than necessary, as this will adversely impact heat transfer efficiency. See the DowFrost
Data Sheet in the back of this manual for recommended concentrations. A copy of the MSDS sheet must be left with the end user of
the solar system. See “EMERGENCY OVERVIEW” as part of the DowFrost Data Sheet in the back of this manual.
The collector loop must be charged with HTF. The use of regular tap water as a mixing agent is prohibited. Use distilled water as a
mixing agent ONLY. Regular scheduled maintenance must be established to monitor and maintain the proper pH level of HTF in the
system to protect the heat exchanger and other components in the system.
F. NECESSARY COMPONENTS FOR SOLAR WATER HEATER INSTALLATION
Listed below are components needed for installation of the solar water heater.
Solar Collector
Absorbs and transfers the sun’s energy into the solar heat exchanger located on the bottom of the solar water heater.
Solar Air Release Vent*
This air vent allows air contained in the solar system to release. The air vent valve must be designed to work in high temperatures (as
high as 350
o
F) with a glycol medium. (This is typical of solar systems.)
*Remove and cap the solar air release vent after commissioning the system.
Solar Collector Sensor
This sensor is wired to the solar controller and automatically turns on the circulator pump when the differential set point is reached
between the solar water heater and collector.
Tank and Heat Exchanger Temperature and Pressure Gauge
The temperature and pressure gauge on the solar piping will show the user the actual temperature and pressure supplied and returned
to the solar collector.
Check Valve
Helps minimize convective heat loss at night when the system is not operating. If a check valve is not installed, most of the heater
energy stored during the day would be transferred into the panel and lost.
Collector Isolation Valve (Valve #6)
Valve #6 and 11 (for solar collector isolation) isolates the collector loop from the solar water heater.
Pressure Relief Valve (for Solar System)
Releases pressure in the solar loop when it exceeds 150psi. Contact your installation contractor immediately if this valve opens
and releases fluids.
System Fill Valve (Valve #8)
Fills the system with HTF. Also eliminates air from the system.
Expansion Tank
Pre-charged with air to allow for the expansion and contraction of HTF.
Drain Valve (Valve #10)
Used to charge the collector loop with glycol, purge air from the loop and drain the solar water heater heat exchanger of fluid.
Collector Isolation Valve (for system fill) (Valve #11)
Used to direct the flow of HTF and to pressurize and eliminate air from the solar system.
Ball Valve (for circulator) Valve #12
Used to isolate the circulator pump for service. Close both ball valves to isolate pump.
20
LP-200 REV. 1.6.15
Circulator (#13)
Circulates the HTF from the solar collector into the solar heat exchanger.
Drain Valve (Tank) (Valve #14)
Flushes sediment which may accumulate on the bottom of the solar water heater and also provides a means of draining the tank.
Tank Sensor
Is wired to the solar controller to measure the temperature on the bottom of the solar water heater in conjunction with the solar collector
sensor. Turns the circulating pump on and off at the solar control preset temperature differentials.
Solar Controller
The solar controller turns on or off the circulator depending on heat gained from solar operation. The controller also limits overheating in
the solar water heater. Some controllers have various options. The controller should always be set in the “auto” position so that it
operates the array automatically when there is solar energy to be collected.
Solar Heat Exchanger
The solar heat exchanger has an integral finned tube designed to transfer heated energy rapidly from the solar collector into potable
water. The heat exchanger is constructed in 90/10 copper nickel for superior corrosion resistance and long-term reliability.
Hot Water Outlet
Each solar water heater has a hot water dip tube outlet which draws water from the top of the heater. This helps to keep heat trapped
inside the highly insulated storage tank.
Solar Tank Temperature and Pressure Relief Valve
The relief valve must comply with standards for relief valves (ANSI Z21.22) by a nationally recognized lab that maintains periodic
inspections of production listed equipment. No valve of any type should be installed between the relief valve and tank. Local codes
govern installation of relief valves.
The relief valve outlet must be piped to a suitable open drain so that the discharge water cannot contact live electric parts to eliminate
potential damage. Piping used should be approved for hot water distribution. The discharge line must be no smaller than the outlet of
the relief valve and must pitch downward to allow complete drainage. The end of the discharge piping should not be threaded or
concealed and must be protected from freezing. No valve of any type, restriction or reducer coupling should be installed in the
discharge line.
Mixing Valve (Rated ASSE 1017) REQUIRED PER SRCC OG-300
Automatically blends hot and cold water feed lines to control discharge to an acceptable and safe temperature. This also increases the
amount of hot water drawn from the solar water heater by not allowing incoming cold water to fully temper the hot water stored inside
the tank. To help prevent injury due to scalding, it is recommended that the mixing valve be set at 120
o
F.
Back-up Electric Element with Thermostat (SE Models)
The back-up electric element will only activate when the desired minimum set point temperature set on the back-up thermostat cannot
be satisfied by the solar gain achieved from the solar collector.
Boiler Back-up Heat Exchanger (SB Models)
The back-up boiler will only activate when the desired minimum set point temperature set on the back-up thermostat cannot be satisfied
by the solar input from the solar collector.
Boiler Back-up Aquastat
The boiler back-up aquastat will activate the boiler to circulate the hot water generated from the boiler into the heat exchanger located
on the top section of SB models. Once the system has reached the desired set point, the controller will shut off the boiler. This back-up
portion will only activate if the solar gain from the collector cannot keep the tank at the minimum desired temperature setting.
Ball Valve (for cold water shut-off) (Valve #24)
The cold water shut off valve should be used in the event of an emergency shutdown.
It is very important that you do the potable piping before you pipe into the solar system. Failure to do so may damage your water
heater. Improper installation IS NOT covered by warranty.
Dielectric unions or galvanized steel fittings must be used on the domestic water connections or auxiliary connections. Teflon thread
sealant must be used on all connections. Failure to do so could result in premature water heater failure. Such failure IS NOT covered by
warranty.
21
LP-200 REV. 1.6.15
G. SOLAR WATER HEATER WITH BOILER BACK-UP
Figure 7 Solar Water Heater with Boiler Back-up FIGURE NOTES:
1. This drawing is meant to show system piping concept only. The installer is responsible for all equipment and detailing by local codes.
2. Antifreeze, non-potable HTF shall be used for the solar heat exchanger circuit only. Never introduce antifreeze solution to any connection other than
the solar loop.
3. If there is a check valve on the cold water feed line, a thermal expansion tank suitable for potable water must be sized and installed within this piping
system between the check valve and cold water inlet of the solar water heater.
4. An ASSE 1017 mixing valve is required per SRCC OG-300.
5. A minimum of 12 diameters of straight pipe must be installed upstream of all circulators.
6. Make sure tank is fully purged of air before power is turned on to the backup heat source.
7. Circulators shown in the above hydronic piping should have an integral flow check or alternately use a stock pump with an external spring type check
valve. (Due to extreme temperatures, circulators with integral flow checks are not to be used in solar systems. If circulator comes equipped
with an integral flow check, remove it.)
22
LP-200 REV. 1.6.15
H. SOLAR WATER HEATER WITH ELECTRIC BACK-UP
Figure 8 Solar Water Heater with Electric Back-up
FIGURE NOTES:
1. This drawing is meant to show system piping concept only. The installer is responsible for all equipment and detailing by local codes.
2. Antifreeze, non-potable HTF shall be used for the solar heat exchanger circuit only. Never introduce antifreeze solution to any connection other than
the solar loop.
3. If there is a check valve on the cold water feed line, a thermal expansion tank suitable for potable water must be sized and installed within this piping
system between the check valve and cold water inlet of the solar water heater.
4. An ASSE 1017 mixing valve is required per SRCC OG-300.
5. A minimum of 12 diameters of straight pipe must be installed upstream of all circulators.
6. For all SE models, make sure tank is fully purged of air before power is turned on to the backup heat source.
7. Circulators shown in the above hydronic piping should have an integral flow check or alternately use a stock pump with an external spring type check
valve. (Due to extreme temperatures, circulators with integral flow checks are not to be used in solar systems. If circulator comes equipped
with an integral flow check, remove it.)
23
LP-200 REV. 1.6.15
I. BOILER BACK-UP HEAT EXCHANGER
CONNECTION (SB MODELS ONLY)
The boiler heat exchanger connections are located in the
front of the solar water heater. Use a 1” minimum pipe
size when connecting zone valves or circulators.
The inlet of the circulator must be connected to the hot
outlet side of the boiler. Be sure the direction of the arrow
on the circulator is facing toward the flow direction from
the boiler to the boiler inlet of the water heater. On the
water heater, the boiler return must be connected to the
return side of the boiler. The return from the heating loop
should have a flow check or swing check valve installed
before the return pipe from the boiler heat exchanger.
J. BOILER TANK CONTROL
Insert the boiler tank control into the control well provided
in the front of the water heater. Wire the boiler tank
control to the boiler control or relay center. Additional
equipment may be needed in order to wire the control to
the existing system. Controls also have the ability to
monitor and display solar collector temperature and upper
and lower tank temperature. See Figure 9 for installation
detail.
K. CIRCULATOR SIZING
The circulator pump must be sized for the related piping and pressure drop of the heat exchanger, and for situations specific to your
solar system. The following graph represents the pressure drop of the solar heat exchanger. Consult the solar panel manufacturer for
flow requirements to assist in pump selection.
Figure 10 Pressure Drop through the Solar Water Heater Heat Exchanger
L. BOILER BACK-UP HEAT EXCHANGER (SB MODELS ONLY)
To assure the correct flow through the boiler back-up heat exchanger, refer to Figure 10 to correctly size the circulator to the boiler or
auxiliary heat exchanger. HTP recommends a flow rate of 1 gpm for every 10,000 BTU based on a 20
o
F temperature difference
between the supply and return of the heat exchanger.
Example: Boiler is 100,000 BTU / 10,000 BTU = 10 gpm flow rate. The heat exchanger at 10 gpm will require a circulator that will
operate at 8 feet of friction.
Figure 9 Sensor Installation Detail
24
LP-200 REV. 1.6.15
M. ELECTRICAL CONNECTION (SE MODELS ONLY)
Tank must be full before unit is turned on. The heating element will be damaged if energized for even a short period of time while tank
is dry. This damage IS NOT covered by warranty.
Be sure to ground the water heater. The preferred way to ground is with rigid metal conduit between the main panel and the water
heater junction box with approved end fittings (check codes on the use of flexible conduit). If making a separate ground, a green ground
wire is provided in the water heater junction box. Replace the junction box cover and insulation after you have made the wiring
connections.
This unit is factory wired to a junction box on top of the water heater. A 4 x 4 x 2 junction box is located on top of the unit for field wiring
connection. These heaters are equipped and wired as standard 120 volt AC (for point of use heaters) and 240 volt AC (for dual element
heaters). The voltage requirement and dedicated wattage load for the heater is specified on the rating label. A minimum 30 amp circuit
is required to connect the water heater. Consult your local power company to determine if your electrical service is adequate for the
additional load of the heater.
Installation, attachment, or use of any unapproved devices in conjunction with this water heater WILL VOID the warranty. The use of
unauthorized energy saving devices may shorten the life of the water heater and possibly endanger property and life. The manufacturer
disclaims any responsibility for any loss or injury resulting from the use of such unauthorized devices.
Refer to the wiring diagrams below for field connections. 240V electrical installation should be done by a qualified licensed electrician or
by your local electric utility. All wiring must conform to local code and the National Electric Code. Grounding can be accomplished by
using approved conduit and fittings or other approved conductive material. A grounding wire is provided on the junction bracket. This
grounding wire must be used in the installation.
After the water and electrical connections have been made and the tank has been filled with water and purged of air, turn on power to
the heater. The heater is now operational.
Do not use SE model water heaters with any voltage other than shown on the model rating plate. Failure to use the correct voltage
shown on the rating plate could result in property damage, serious personal injury, or death.
Figure 11 - SE Series Electrical Connection Detail
25
LP-200 REV. 1.6.15
N. THERMOSTAT ADJUSTMENT
The thermostat is located in the front of the heater. The access cover must be removed to adjust the factory default setting of 119
o
F.
This temperature is satisfactory for average household use.
If an adjustment is necessary, turn off the power to the heater, remove the black access cover and insulation. The thermostat protective
cover should not be removed. Set the temperature indicator to the desired temperature, replace insulation and access cover. Turn on
power to the heater.
O. COMBINATION “THERMOSTAT AND HIGH LIMIT CONTROL (ECO)”
This heater is equipped with a combination thermostat and high limit safety. If for any
reason the water temperature becomes excessively high, the “High Limit Control
(ECO)” breaks the circuit to the heating element. Once the switch opens it must be
reset manually. However, THE CAUSE OF THE OVERHEATING CONDITION MUST
BE CORRECTED FIRST. Refer to the Troubleshooting section for possible causes. To
reset, press the red reset button as shown in Figure 12. Replace the insulation and
black access cover before restoring power to the system.
PART 7 - FLUID QUALITY
A. SOLAR LOOP FLUID QUALITY
Fluid in direct flow through the solar collectors must first meet potable water
requirements; any fluid circulated through the collectors should be non-corrosive to
copper. In addition, water quality must meet the following requirements listed below.
Hardness: Less than 7 grains
Chloride levels: Less than 100 ppm
pH levels: 6-8
TDS: Less than 2000 ppm
Sodium: Less than 20 mGL
In order to meet health and safety regulations, solar system antifreeze fluid should be food grade polypropylene glycol, FDA rated as
“generally recognized as safe” (GRAS). Using proper concentrations of glycol, solar systems can be operated at ambient temperatures
as low as -60
o
F. Freeze tolerance limits are based upon an assumed set of environmental conditions. Refer to the DOWFROST
specification sheet in the back of this manual for recommended concentrations. If using a glycol/water mix, the water must meet the
above requirements, and the glycol content of the liquid must not exceed 50%, unless the manufacture specifies that a different ratio is
recommended for use with solar water heaters. Glycol may need to be changed periodically (every 3-5 years) to prevent it from
becoming acidic; please refer to the guidelines provided by the glycol manufacturer regarding replacement.
B. FLUID SAFETY LABELING
Included with your solar system is a set of labels which describe component function. These labels alert the owner to potential hazards.
Affix these labels by string/wire/tie on valves, and/or “peel and stick” on pipe insulation. Labels on the solar loop system must contain
the following warning:
“No other fluid shall be used that would change the original classification of the system. Unauthorized alterations to this system could
result in a hazardous health condition.”
All labeling MUST be in place at final inspection.
C. FREEZE PROTECTION
“Freeze tolerance limits are based upon an assumed set of environmental conditions. Extended periods of cold weather, including
ambient air temperatures above the specified limit, may cause freezing in exposed parts of the system. It is the owner’s responsibility to
protect the system in accordance with the Supplier’s instructions if the air temperature is expected to approach the specified freeze
tolerance limit.”
For areas with temperatures not falling below 5
o
C / 23
o
F, a simple low temperature controller may be used to guard against freezing.
If necessary, backup freeze protection in the form of an uninterrupted power supply (UPS), or freeze valves (which open to allow water
to dribble out) should also be installed.
For areas with temperatures that fall below 5
o
C / 23
o
F, a closed loop filled with a polypropylene glycol-water mix should be used to
provide hard freeze protection. Please refer to glycol manufacturer’s specifications about the temperature ranges the liquid can
withstand. Only food grade polypropylene-glycol, FDA rated as GRAS, should be used.
Figure 12 Thermostat Detail
26
LP-200 REV. 1.6.15
NOTE: HTP DOES NOT WARRANT THE SOLAR WATER HEATER, SOLAR COLLECTOR, OR ANY COMPONENTS AGAINST
FREEZE RELATED DAMAGE.
PART 8 START-UP PREPARATION
DO NOT MOVE ON TO THESE STEPS UNTIL THE ENTIRE SOLAR SYSTEM, INCLUDING ALL PIPING, SOLAR COLLECTORS,
SENSORS, PUMP, CONTROLS, AND ELECTRICAL CONNECTIONS, ARE PROPERLY SECURED, INSULATED, LABELED AND
INSTALLED.
A. CHARGING THE SYSTEM
Solar Water Heater
Fill the solar tank with water. Do this by opening the cold water isolation ball valve to the solar tank. See Figs. 6 8 for valve locations.
Inspect all fittings for leaks.
Solar Collector
The solar collector loop should be pressure tested with air (25 psi) before you pressurize the loop with HTF. If using glycol, mix in
accordance with the glycol manufacturer’s data sheet. The charging process will require a low flow diaphragm pump to fill and
pressurize the collector loop.
Connect the discharge side of the pressure pump to the fill valve. See Figs. 6 8. Place the pump suction side hose in the glycol
solution. Close the ball valve (#11). Connect a second hose to the drain valve (#10) and place the other end of the hose in the empty
bucket.
TOTAL COLLECTOR LOOP FLUID CAPACITY IN GALLONS*
1. Collector System 3.5 gallons
2. Collector System 4.5 gallons
*Assumes a total 100’ pipe run using ¾” Type M hard copper tubing.
The solar water heater heat exchanger has a 1.75 gallon fluid capacity.
Open the upper fill valve (#18) and allow the pressure from the expansion tank
to push the water in the loop back to prime the pressure pump. When the hose
in the bucket containing the HTF stops bubbling, you may begin charging the
collector loop. With both fill and drain valves open, run the low flow diaphragm
pump until the HTF begins flowing into the empty bucket. Quickly switch the
hose from the empty/return bucket to the bucket containing the glycol mixture.
Continue to circulate the fluid using the pressure pump until the bubbling has
stopped and the air has been purged.
After charging the collector loop, shut the lower drain valve (#10) and let the
pressure pump drive up the loop pressure to the appropriate level (in glycol
systems, in the range of 25 psi). To more accurately calculate the proper
pressure, measure the height of the solar collector above the solar water heater
and divide this number by 2.31. Then add 20 psi to this number.
The pressure in a glycol loop should not exceed 45 PSI when the system is in operation on a sunny day. Contact your solar contractor if
the loop exceeds this threshold.
After pressurizing the solar system, run the circulator and allow the air to purge out of the air vent. Once purged, monitor pressures and
check for leaks before insulating pipes. Pressure should then be about 25 PSI.
Above ground piping must be insulated with a wall thickness of at least ¾”. A 1” thickness is required in areas prone to hard freeze
conditions. Above ground insulation must be protected from ultraviolet degradation. All piping must be supported at a maximum interval
of 10 feet and the piping supports must not crimp or compress the insulation.
B. COMMISSIONING THE SYSTEM
After the collector loop has been charged and pressure is around 25 PSI (check gauge on solar heat exchanger) set the solar control to
the desired settings. Solar controls come with default settings that will work in most installations. If it is a cloudy day, the circulator pump
may have to be activated manually. Once the pump is running and the system is fully purged of air, set the control to the desired
settings. It is recommended not to set the storage tank high limit set point any lower than 160
o
F. A lower set point could lower the
27
LP-200 REV. 1.6.15
performance of the solar water heater and cause overheating of the collector system. You must install a mixing valve on the hot water
outlet, as temperature within the storage tank can cause injury.
PART 9 SERVICE/MAINTENANCE PROCEDURES
A properly maintained solar water heating system can provide years of dependable, trouble-free service. It is suggested that a routine
preventive maintenance program be established and followed by the end user with the solar contractor. Listed below is the
maintenance check list that outlines the primary components of the solar system that need to be inspected annually.
1. HTF Glycol (if used) It is very important that the quality of the glycol is maintained to avoid damage to the collector loop and related
components. See the manufacturer’s data sheet for further details.
2. Water quality can affect the operation of the solar heat exchanger over time. In very hard water areas, it is recommended to drain
(#14) a few gallons of water from the bottom of the tank to keep the water heater free of sediment.
3. Clean and inspect the solar collector (#1). Dirt or film may settle on the surface and affect performance. Check collector supplier for
cleaning procedures.
4. Check piping and component insulation for deterioration.
5. Check solar tank sensors and the boiler back up aquastat sensors (#’s 15 and 23). Assure these sensors are secure and have not
moved or loosened.
6. Inspect the T&P valve (#19) on the water heater. Lift the release handle lever. Make sure discharge is directed to an open drain.
Never open the pressure relief valve while the system is in operation or hot water is present. Allow to cool prior to opening.
7. The area near the water heater must be kept free of flammable liquids such as gasoline, paint thinners, adhesives, or other
combustible materials.
8. The electric element may need cleaning. A hissing sound while operating indicates the element has built up deposits. Cleaning
should only be done by a qualified plumbing or heating contractor.
If the heating element needs replacement, it is VERY important to use the same voltage, wattage, and construction. This element must
be stainless steel and the hex plug be made of brass. This replacement part is available from HTP and should not be purchased from
outside sources.
A. SHUTDOWN PROCEDURES
The solar system is designed to be easily isolated for emergency repairs or routine maintenance. To isolate the water heater, simply
shut down supply water shut off valve (#24) which isolates the water heater from the pressurized cold water supply.
The collector loop can be isolated from the solar storage tank by closing (#6 and #11). If the pressure in this loop drops, or you find a
glycol leak, shut these valves and contact your installation contractor. Turn the circulating pump off on your solar control.
B. VACATION SHUTDOWN
Solar water heaters can build up very high temperatures when there is no daily draw on the system. The best way to dissipate heat in
the system is set the control to run the circulator pump 24 hours a day to cool off the storage tank at night. The collector will radiate
heat back to the atmosphere at night, preventing the system from stagnating at very high temperatures.
C. ESTIMATED LIFE OF COMPONENTS
Proper care and maintenance will determine the life expectancy of the individual components of the solar system. Refer to
manufacturer’s warranty information to determine coverage of individual components. To obtain warranty service, call your local service
or installing contractor.
D. TEMPERATURE AND PRESSURE RELIEF VALVE
A temperature and pressure relief (T&P) valve is designed for emergency safety relief and shall not be used as an operating control. A
T&P valve functions by discharging water in an emergency. Therefore, it is essential that a discharge line be piped from the valve in
order to carry the overflow to a safe place of disposal. The discharge line must be the same size as the valve outlet, must pitch
downward from the valve, and terminate at least 6” above a drain where any discharge will be clearly visible.
28
LP-200 REV. 1.6.15
Following installation of the T&P Relief Valve, the valve lever MUST be operated AT LEAST ONCE A YEAR by the water heater
owner to ensure that waterways are clear. Certain naturally occurring mineral deposits may adhere to the valve, blocking waterways
and rendering the valve inoperative. When the lever is operated, hot water will discharge if the waterways are clear. PRECAUTIONS
MUST BE TAKEN TO AVOID PERSONAL INJURY FROM CONTACT WITH HOT WATER AND TO AVOID PROPERTY DAMAGE.
BEFORE operating lever, check to see that a discharge line is connected to the valve, directing the flow of hot water from the valve to a
proper place of disposal. If no water flows when the lever is operated, replacement of the valve is required. TURN THE WATER
HEATER “OFF” AND CALL A PLUMBER IMMEDIATELY.
PART 10 - TROUBLESHOOTING
Owners are advised to contact the installer whenever in-depth interaction with the solar system is required.
A. LEAKS
For leaks in the potable water system or solar storage tank, close the cold water inlet and unplug the solar controller. This will isolate
the solar system until repairs can be made.
B. OTHER PROBLEMS
A noisy pump could be an indication of worn bearings, obstructions, or a leak in your system. Call your installer for diagnosis of the
problem, repair of the system, and/or replacement of components.
For your safety, DO NOT attempt repair of electrical wiring, thermostat, heating element or other operating controls. Refer repairs to
qualified service personnel.
C. OPERATING SUGGESTIONS FOR THE USER
A properly designed solar hot water system provides solar energy for approximately 70 90% of annual hot water needs. Listed below
are some suggestions that will maximize the benefits of your solar hot water system.
1. Showers - If possible, take showers during the day, or in the early evening. Use low flow showerheads to reduce water
consumption.
2. Dishwashing Run your dishwasher during the day, after showers, to ensure as much hot water as possible is available for
showers.
3. Laundry Spread clothes washing over the week instead of washing all at the same time.
4. Single Lever Faucets When using cold water, make sure the lever is all the way over in the cold position. This prevents hot
water from inadvertently flowing from the solar storage tank.
NATURE OF TROUBLE
POSSIBLE CAUSE
SERVICE
No hot water
1. Improper wiring
Rewire per Wiring Diagram
2. No power blown fuse or circuit breaker
tripped
a. Shorted wiring
b. Circuit overloaded
c. Improper wiring
d. Grounded element or thermostat
a. **Replace or repair
b. **Provide adequate circuit or reduce load
c. **Rewire per diagram
d. **Replace
3. Manual reset limit (ECO) open
a. Thermostat defective
b. Thermostat out of calibration
c. Heat build-up due to loose wires
d. Defective limit (ECO)
Refer to “Operation” Section
a. **Replace
b. **Lower setting or replace
c. **Tighten wire connections
d. **Replace
4. Solar system incorrectly installed
**Check installation
5. Defective element
**Replace element.
6. Leaking plumbing or open hot water
faucet(s)
Make sure all faucet(s) are closed and check water
meter
Not enough hot water
1. Heater undersized
Reduce rate of hot water use
2. Defective element
**Check amperage, replace element
3. Defective thermostat or wired incorrectly
**Check wiring or replace
4. Solar system incorrectly installed
**Check installation
5. See #6 above (in No hot water)
See above
29
LP-200 REV. 1.6.15
NATURE OF TROUBLE
POSSIBLE CAUSE
SERVICE
Water too hot or not hot
enough
1. Thermostat setting too high or low
Change setting as required
2. Thermostat out of calibration
**Replace
3. Solar system incorrectly installed
**Check installation
4. Grounded element
**Replace
Noisy heating element
Scale built up on element
**Remove and clean
Table 3
See water heater installation manuals for more detailed maintenance information.
**For your safety, DO NOT attempt repair of electrical wiring, thermostat or operating controls. Refer repairs to qualified service
personnel.
PART 11 - SYSTEM PARTS LISTING
A. ESTIMATED COMPONENT LIFE
These water storage tanks are designed for 10 years of use. When installed and maintained as directed by this manual, one can expect
many years of trouble-free service from this solar system. However, all components in this system are subject to installation conditions.
For example: Where hard water is present, mineral deposits can shorten the life of components. Periodic maintenance as prescribed by
this manual ensures that these components are well protected from such damage.
B. WARRANTIES AND DISCLAIMERS
NOTE: WE EXCLUDE ANY WARRANTY FOR, OR LIABILITY FROM ACTS OF NATURE, INCLUDING FREEZE DAMAGE.
Warranty periods for tank components are listed in the table below:
MANUFACTURER
ITEM
PART#
COMPONENT
COVERAGE
TANK
COVERAGE
HTP
Glass-Lined Solar Storage Tank
w/ Back-Up Heat Exchanger
SSC-50SB
1 year
Residential 7 years
Commercial 5 years
HTP
Glass-Lined Solar Storage Tank
w/ Back-Up Heat Exchanger
SSC-80SB
1 year
Residential 7 years
Commercial 5 years
HTP
Glass-Lined Solar Storage Tank
w/ Back-Up Heat Exchanger
SSC-
119SB
1 year
Residential 7 years
Commercial 5 years
HTP
Glass-Lined Solar Storage Tank
w/ Back-Up Heat Exchanger
SSC-50SE
1 year
Residential 7 years
Commercial 5 years
HTP
Glass-Lined Solar Storage Tank
w/ Back-Up Heat Exchanger
SSC-80SE
1 year
Residential 7 years
Commercial 5 years
HTP
Glass-Lined Solar Storage Tank
w/ Back-Up Heat Exchanger
SSC-
119SE
1 year
Residential 7 years
Commercial 5 years
Table 4
30
LP-200 REV. 1.6.15
Figure 13 SE Model Parts Breakdown LP-200-E
Item No
SSC-50SE
SSC-80SE / 119SE
Description
QTY.
1
6075P-002
6075P-008
HOT WATER OUTLET
1
2
6075P-003
6075P-009
HOT WATER DIP TUBE
1
3
6075P-044
6075P-044
ANODE ROD, STANDARD SOLID
1
4
6075P-054
6075P-054
GASKET - ELECTRIC ELEMENT
1
5
6075P-052
6075P-052
ELECTRIC ELEMENT (W/GASKET)
1
6
6060P-1008
6060P-1008
UPPER THERMOSTAT CONTROL
1
7
6060P-633
6060P-633
THERMODISC MOUNTING CLIP
1
8
6060P-632
6060P-632
5/16-18 HEX NUT - THERMODISC MOUNTING CLIP
2
9
6060P-994
6060P-994
PLASTIC PROTECTIVE COVER
1
10
6060P-187
6060P-187
ELECTRICAL BOX COVER
2
11
6075P-006
6075P-006
#8 X 3/4" SELF TAPPING SCREW
2
12
N/A
N/A
SOLAR PANEL SURFACE MOUNTED SENSOR
1
13
6075P-053
6075P-053
KAMCO FIBERGLASS INSULATION
1
14
TP1000
TP1000
3/4" RELIEF VALVE
1
15
2500P-0092
2500P-0092
DRAIN VALVE
1
16
N/A
6060P-631
1-3/4" HOLE FLANGE
1
Table 5 SE Model Replacement Parts List
31
LP-200 REV. 1.6.15
Figure 14 - SB Model Parts Breakdown
Item No
SSC-50SB
SSC-80SB / 119SB
Description
QTY.
1
6075P-002
6075P-008
HOT WATER OUTLET
1
2
6075P-003
6075P-009
HOT WATER DIP TUBE
1
3
6075P-044
6075P-044
ANODE ROD, STANDARD SOLID
1
4
6060P-1009
6060P-1009
THERMOSTAT CONTROL
1
5
6060P-633
6060P-633
THERMODISC MOUNTING CLIP
1
6
6060P-632
6060P-632
5/16-18 HEX NUT - THERMODISC MOUNTING CLIP
2
7
6060P-952
6060P-952
PLASTIC PROTECTIVE COVER
1
8
6075P-053
6075P-053
KAMCO FIBERGLASS INSULATION
1
9
6075P-006
6075P-006
#8 X 3/4" SELF TAPPING SCREW
2
10
N/A
N/A
SOLAR PANEL SURFACE MOUNTED SENSOR
1
11
6060P-187
6060P-187
ELECTRICAL BOX COVER
2
12
TP1000
TP1000
3/4" RELIEF VALVE
1
13
2500P-0092
2500P-0092
DRAIN VALVE
1
14
N/A
6060P-631
1-3/4" HOLE FLANGE
1
Table 6 SB Model Replacement Parts List
32
LP-200 REV. 1.6.15
33
LP-200 REV. 1.6.15
34
LP-200 REV. 1.6.15
VISCOSITY: The HTF viscosity over the service temperature range is based on a specific gravity 15/15
o
C (60/60
o
F) 1.053-1.063.
DOWFROST inhibited glycol-based fluid has an effective operating temperature range of -50
o
F to 250
o
F. At temperatures below -50
o
F,
increased viscosity (>1,000 centipoise) can make use of DOWFROST impractical unless larger pumps are installed. At the upper end of
the operating range for DOWFROST fluid, a maximum bulk temperature of 250
o
F is recommended. Film temperature should not
exceed 300
o
F. DOWFROST fluid can tolerate brief temperature excursions up to 100
o
F above the maximum recommended
temperatures. However, extended exposure of the fluid to temperatures in excess of 50
o
F above the maximum recommended
temperatures will result in accelerated degradation of the glycol and inhibitor systems. In addition, the film temperature should remain
within 50
o
F of the bulk fluid temperature and the pressure at all points in the system should be at least 5 psi greater than the vapor
pressure exerted by the fluid to avoid localized boiling and resulting precipitation. At temperatures above 150
o
F, the system must be
closed to avoid rapid oxidation of the propylene glycol, inhibitor depletion, and subsequent increased corrosion. Automatic make-up
water systems should be avoided in order to prevent undetected dilution or loss of glycol and consequent loss of freeze and corrosion
protection.
FLAMMABILITY: When mixed with water, DOWFROST is not flammable, as the fluid has no measurable flash point (Pensky-Martens
Closed Cup) in concentrations up to 80% glycol. Undiluted DOWFROST has a flash point of 214
o
F (Pensky-Martens Closed Cup). It is
possible to ignite solutions of propylene if enough water has been vaporized and the concentration of propylene glycol increases to
greater than 80 percent.
INSPECTION AND TREATMENT OF HEAT TRANSFER FLUID: You can quickly determine the condition of your fluid by examining its
appearance and odor. Any drastic variation from the initial fluid specifications, such as a black or dark-grey color, presence of an oily
layer, burnt odor, or any heavy sludge in the fluid may indicate the need for replacement.
TESTING THE FLUID pH LEVEL: Control of pH between 8 and 10 is important to minimize corrosion and glycol degradation. Using
narrow range pH paper, such as pHydrion Control paper with a 7.2 to 8.8 pH range, is an easy and reliable way to read your pH level. A
pH tester can also measure alkalinity or acidity and give you an indication of the reserve alkalinity or inhibitor level of the fluid. The
desirable pH range should fall between 8.0 and 10.0. Adjustments can be made using a 50% solution of sodium hydroxide or potassium
hydroxide if the pH is approaching the acidic range (below 8.0). An inexpensive pH tester is available from Misco Products. The
accuracy of this product is +/- 0.5 pH. Contact Misco Products at 1-800-358-1100 and ask for the Dow discount.
SPILL, LEAK, AND DISPOSAL PROCEDURES: Using appropriate safety equipment, small spills may be soaked up with common
absorbent material. For large spills, the fluid should be pumped into suitable containers located in diked areas. Residual material should
be cleaned up with water. Concentrate can be handled according to local, state, and federal regulations.
EMERGENCY OVERVIEW
POTENTIAL HEALTH EFFECTS
EYE: May cause slight transient (temporary) eye irritation.
Corneal injury is unlikely. Mists may cause eye irritation.
FIRST AID: FLUSH EYES WITH PLENTY OF WATER
SKIN CONTACT: Prolonged contact is essentially non-irritating to skin. A single prolonged exposure is not likely to result in the material
being absorbed through the skin in harmful amounts. Repeated exposure may cause flaking and softening of skin.
FIRST AID: WASH OFF IN FLOWING WATER OR SHOWER
INGESTION: Single dose oral toxicity is considered to be extremely low. No hazards anticipated from swallowing small amounts
incidental to normal handling operations.
FIRST AID: NONE REQUIRED
INHALATION: At room temperature, vapors are minimal due to physical properties. Mists may cause irritation of upper respiratory tract
(nose and throat).
FIRST AID: REMOVE TO FRESH AIR.
IF EFFECTS OCCUR, CONSULT A PHYSICIAN.
NOTE TO PHYSICIAN: NO SPECIFIC ANTIDOTE.
SUPPORTIVE CARE. TREATMENT BASED ON
JUDGEMENT OF THE PHYSICIAN IN RESPONSE TO
THE REACTION OF THE PATIENT. CONSULT DOW CHEMICAL
24 HOUR EMERGENCY 1-989-636-4400.
35
LP-200 REV. 1.6.15
SYSTEM MODELS
SOLAR COLLECTOR COMPANY
MODEL
# OF COLLECTORS
2007011A
HTP
AE-32E
1
2007011B
HTP
AE-40E
1
2007011C
HTP
AE-32E
2
2007012A
HTP
AE-32E
1
2007012B
HTP
AE-40E
1
2007012C
HTP
AE-32E
2
Table 7
SOLAR SYSTEM REPLACEMENT PARTS
Part
Company
Model
CONTROLLER
STECA
TRO301
GOLDLINE
GL-30
HELIOTROPE
Thermal Delta T
PUMP
TACO
OO7
GRUNDFOS
15-58F
EXPANSION TANK
AMTROL
Extrol #30
CHECK VALVE
WATTS
SERIES 600*
*(ALTERNATE APPROVED EQUIVALENT)
PRESSURE RELIEF VALVE
WATTS
3L (75 psig)
AIR VENT
TACO
417*
*(ALTERNATE APPROVED EQUIVALENT)
MIXING VALVE
TACO
500 SERIES
WATTS
1170 SERIES
HONEYWELL
AM101 SERIES
CACHE ACAC
HEATGUARD 110 SERIES
PIPING
COPPER
HEAT TRANSFER FLUID
DOW CHEMICAL
DOWFROST
(DOWFROST HD approved for use with DW models)
Table 8
INSTALLER: Make a note of the installed system in the table above.
36
LP-200 REV. 1.6.15
37
LP-200 REV. 1.6.15
MAINTENANCE NOTES
38
LP-200 REV. 1.6.15
HTP CUSTOMER INSTALLATION RECORD FORM
The following form should be completed by the installer for you to keep as a record of the installation in case of a warranty claim. After
reading the important notes at the bottom of the page, please also sign this document.
Customer’s Name:
Installation Address:
Date of Installation:
Installer’s Code/Name:
Product Serial Number(s):
Comments:
Installer’s Phone Number:
Signed by Installer:
Signed by Customer:
IMPORTANT NOTES:
Customer: Please only sign after the installer has reviewed the installation, safety, proper operation and maintenance of the
system. In the case that the system has any problems, please call the installer. If you are unable to make contact, please
contact your HTP Sales Representative.
Distributor/Dealer: Please insert contact details.