Rated insulation voltage U
i
600 V Analog output
Rated operational voltage U
e
208 ... 600 V +10 %/-15 % Output signal reference 4 ... 20 mA
Rated control supply voltage U
s
100 ... 250 V +10 %/-15 %, 50/60 Hz ±5 %
Type of output signal I Amp
Rated control circuit voltage U
c
Internal 24 V DC
Scaling Fixed at 1.2 x I
e
Starting capacity 4xI
e
for 10 sec. Control circuit
Number of starts per hour 10
1)
Number of inputs 3 (start, stop, reset of faults)
Overload capability, Signal indication LED’s
Overload Class 10 On / Ready Green flashing / steady
Ambient temperature Run / TOR Green flashing / steady
During operation -25 … +60 °C (-13 to 140 ºF)
2)
Protection Yellow
During storage -40 … +70 °C (-40 to 158 ºF) Fault Red
Maximum Altitude 4000 m (13123 ft)
3)
Protections
Degree of protection
Electronic overload Yes (Class 10A, 10, 20, 30) Main circuit IP00 Locked rotor protection Yes
Supply and Control circuit IP20 Underload protection Yes
Main circuit
Built-in By-pass Yes Field bus connection
Cooling system - Fan cooled Connection for
(thermostat controlled)
Yes ABB FieldBusPlug Yes (option)
HMI for settings External keypad
Display 4 7-segments and icons. Illuminated Display LCD type
Keypad 2 selection keys and 2 navigation keys Ambient temperature
Main settings during operation -25 … +60 °C (-13 to 140 ºF)
Setting current Size dependent during storage -40 … +70 °C (-40 to 158 ºF)
Ramp time during stop 0-30 sec
Initial / end voltage 30-70%
Current limit 1,5-7xI
e
Torque control for start Yes / No
Torque control for stop Yes / No
Kick start Off, 30-100%
Signal relays
Number of signal relays 3
K2 Run signal
K3 TOR (By-pass) signal
K1 Event signal
Rated operational voltage U
e
250 V AC / 24 V DC
4)
Rated thermal current I
th
3 A
Rated operational current I
e
at AC-15 (U
e
= 250 V) 1.5 A
Class 30
Class 20
Class 10
Class 10A
87
6
5
4
3
21
10 000
1000
100
10
1
0
0
Time (s)
Current (x I
e
)
Tripping curves for electronic overload protection (Cold)
1)
Valid for 50 % on time and 50 % off time, with 3.5 x I
e
for 7 seconds. If other data is required, please contact your sales office
2)
Above 40 ºC (104 ºF) up to max. 60 ºC (140 ºF) reduce the rated current with 0.6 % per ºC (0.33 % per ºF).
3)
When used at high altitudes above 1000 meters (3281 ft) up to 4000 meters (13123 ft) you need to derate the rated current using the following formula.
[ % of I
e
= 100 -
x - 1000
150
[ % of I
e
= 100 -
x - 3280
497
4)
A common voltage needs to be used for all 3 signal relays.
Softstarters
Type PSE
PSE – The efficient range
Technical data